Serial Connectivity for Risco Agility

System Requirements

 

 
 Manufacturer 

 Risco 

 Panel / Model

 Agility 

 Versions 

 Agility II & Agility III 
 
 Panel Firmware

 V2.33

 Cable Required

  05-5040 
 
 SPT Version

 V3.51 or greater
 
 Remote Manager

 V3.2.2.5 or greater

 Notes 

 SPT will require additional Power Supply Unit - due to no space in the panel for the SPT


Panel Connection

WebWay Cable Wiring

Please complete as follows with standard alarm cable.


WebWay SPT  Risco Agility Port Cable Core Colour

232-T

 Pin 1
Red

RTN

 Pin 2 (Centre)


Blue

R-232

Pin 3 Yellow




WebWay SPT Control Panel

  


Panel Keypad Controls



Panel Programming

NOTE : Risco Agility has two Communication Menu’s, please check you are in the correct Communication Menu during panel programming


1. Login to Engineer Mode <*> + <Engineer Code>

2. Keypad shows <1] Programming> and press <#>

3. Scroll to <1] System> and press <#>

4. Scroll ↓ to <2] Controls> and press <#>

5. Scroll ↓↓ to <3] Communication> and press <#>

6. Scroll ↓↓ to <ARC ENABLE> and set to 'N' and press <#>

7. Screen shows <3] Communication> and press <#>

8. Scroll ↓ to <Config SW Enable> and set to 'Y' and press <#>

9. Screen shows <3] Communication> and press <#>  

10. Scroll ↓↓ to <FM ENABLE> and set to 'N' and press <#>

11. Press <*> 2 twice you are now in the Main Menu

12. Scroll ↓↓↓ to <4] Communications> and press <#>

13. Scroll ↓ to <3] Config. SW> and press <#>

14. Screen shows <1] Security> and press <#>

15. Scroll ↓ to <2] Remote ID> and press <#>

16. Modify value to <00000> and press <#

17. Screen shows <2] Remote ID> Press <*> Press ↓

18. Screen shows <2] Call Back> Press <#> and set <Call Back En> to 'N' and press <#>

19. Press <*

20. Scroll ↓ <3] IP Gateway> Press <#> into <1] IP Address> Remove any IP Config.

21. Scroll ↓ <2] IP Port> Press <#> Modify value to <00000> and press <#>

(21A. If you have a GSM modules Remove Setting from this Menu)

22. Press <*> 3 times

23. Screen shows <4] Communication>

24. Now Exit Engineer Mode <0> and Press <#> this saves the data


Manufacturers Panel Limitations: 


 Panel Will NOT Communicate: 

 
 A username after an alarm's activation or a Panel Event. 
 Device information such as keypad user identity or if a fob is used with an Alarm Activations or Panel Events. (Exception is "Jamming" and  Low Battery" are reported) 
 Auto Set, Unset Fail
 Remote Set and Unset
 ARC periodic test & ARC keep alive
 Call back
 System reset
 Listen in begin 
 Walk test